 Buffer Tanks FAQ

What is a buffer tank?

A buffer tank is a water tank installed between your heating boiler and the heating system.

 

What is the purpose of a buffer tank?

The tank adds water volume to the heating system to address boiler short cycling.

 

Are buffer tanks a new idea?

Although the buffer tank idea has been around a long time the popularity of the buffer talk has increased mostly over the last decade.

 

Why would I need a buffer tank?

When your heating boilers are too large or you have some small heating zones the boiler

will short cycle. Short cycling will cause lower efficiency and higher fuel bills more maintenance.

 

Will a buffer tank save me fuel dollars? 

If your heating boiler is short cycling it will save you money and decrease maintenance.

 

How do I size a buffer tank?

The formula to size a buffer tank is as follows

 

BT = t *(Qh - qload)/(500*dT)

 

                                                                                                                             Bt = Bufer Tank Size in gallons

                                                                                                                             t - Time operating - on cycle time

                                                                                                                            Qh = Boiler DOE output in btu's

                                                                                                                            qload = Connected radiation load

                                                                                                                            dT - Delta T of tank between on and off cycle

Example;

t = 10 minutes (my boiler run time)

Qh - 120,000 - Boiler DOE output

qload - 15,000 - Baseboard output (small single zone)

dT - 30f - Temp drop in tank before tank requires more heat 

bt = 10*(120,000/15,000)/(500*30)

bt = 10*(105,000/15,000)

bt=70 gal tank

 

Larger zones could be piped without the buffer tank and only

smaller zones through buffer tank

 

This drawing is for illustration only.

Follow industry standards or manufacturer’s directions when adding a buffer tank.